1. 您现在的位置:首页
  2. 图集相册
  3. Electricity information collection
  4. FKGA83-GK200 I type special variant collection terminal(Wireless public network)

FKGA83-GK200 I type special variant collection terminal(Wireless public network)

                                                       

  FKGA83-GK200 I type special variant collection terminal(Wireless public network)


FKGA83-GK200 I type special variant collection terminal(Wireless public network)

product presentation

FKGA83-GK200  I type variable collection terminal is designed to meet the needs of  the national DSM and developed . Using a multi-layer circuit boards and  SMT production process , highly integrated, advanced technology , fully  functional application. It is the power company to monitor users of  electricity , raising the level of demand-side management ,  high-performance terminal execution unit .

main features

Terminal  has a modular structure , less wiring , easy maintenance , LCD ,  features large-capacity data storage space. Available to upgrade remote  and local program, Independent RS485 reading interface, 8000 Chinese  characters display, omnibearing information service. On the interface,  configure the 8 pulse inputs, eight remote communication status inputs, 4  control outputs ( normally open and normally closed ), RS232 port ,  RS485 port , It can achieve the required functionality DSM terminal. All  of its performance indicators are in line with the latest standards of  enterprises , it is the power sector to implement load control , remote  meter reading and effective techniques for power management.

Technology standard

Q / GDW129-2005 “ Power Load Management System General technical conditions ”

Q / GDW130-2005 “ power load management system data transmission protocol ”

State Grid Corporation of Production Operations : electric load management system functional specification;

Industry standard DL / T 533-1993: two-way radio load control terminal technical conditions;

Industry standard DL / T 645-1997: multifunction energy meter communication protocol;

Industry standard DL/T 645-2007:multifunction energy meter communication protocol;

 

The main function

( 1 )   Data Collection

( 2 )   parameter tuning and query

( 3 )   Remote tripping function

( 4 )   local loop control

( 5 )   Paul electrical function

( 6 )   Excluding function

The main technical parameters

1 Temperature  : -20 ℃ ~ + 55 ℃; Humidity: 5% to 100% ( including condensation ) ,  absolute humidity :less than 28g / m --- 3; atm : BB2 grade , 66 ~  108kPa

2 Operating Supply Voltage

220V or 100V, AC tolerance of -15% to + 20%

3 Wireless channel

      Information  transfer format consistent with the provisions of DL533 , using  frequency shift keying - FM system, half-duplex mode .

4 Operating Frequency

Using  frequency bands and local radio management committee approved the  distribution of State Radio Regulatory Commission , specifically  provided by the user.

( 5 ) Input circuit

Number  of inputs : 4 ; pulse width : 60 ~ 80ms; pulse amplitude 10V ± 2V;  input: active or passive pulse ; measurement accuracy: 0.1%

Remote signal inputs: Number of inputs : 8 ; Input: uncharged should open / close switch contacts

6 Output circuit

Control output:

Outputs:  4 open / close dual position control output ; output relay Type :  bistable relay ; contacts rated power : can be switched on and breaking  exchange 250V, 10A; contact life : pass, breaking above the rated  current is not less than 105

Power output: for 12V / 150mA power meter for pulse input

7 Meter RS485 interface

A  dedicated meter standard RS485 interface, communication speed 300 ~  9600bps optional power meter can be accessed 16 (expandable to 32 )

8 AC sampling device interface RS485

A  standard RS485 interface dedicated AC sampling device , the  communication speed 300 ~ 9600bps optional , can be accessed by two -way  exchange of sampling device .

9RS232 interface

A standard RS232 interface , the communication speed 9600bps, can be used for on-site communication and management.

Working principle

     

Terminal  device through the input and output board to complete the user's meter  data acquisition, sampling to control the user switches and switch  position, management and data storage function. Terminal at the time of  maintenance can also be downloaded via the RS232 interface upgrade  program and parameter setting.

FKGA83-GK200  I type data acquisition terminals of special transformer device through  the input and output board to complete the user's meter data  acquisition, sampling to control the user switches and switch position,  management and data storage function. When a station receives a command  signal from a control center of the main station, CPU makes a judgment  and processing of data received through the modulation and demodulation  board, according to the corresponding command  to complete the equipment remote communication, telemetry, remote  control and parameter setting, data query and management, and then the  digital information to the control center. Terminal at the time of  maintenance can also download the update program through RS232  interface, through the buttons to adjust radio channels, transmit power,  squelch level. In addition, the terminal can monitor the received field  strength, working voltage, condition management.